Minimum Approach Distances - 220kV Lines on Towers
… side of conductors 11m 14m 22.5m Table 1 – 220kV lines Safe distances for buildings and structures near conductors … beneath conductors 8.5m 10m 11m Engineering advice required Minimum Approach Distances Near 220kV Transmission Lines on Towers …
220kV Lines on Towers
(PDF 220.62 KB)
Last updated: 05 Jul 2023
Minimum Approach Distances - 110kV Lines on Towers
… of conductors 9.5m 12.5m 21m Table 1 – 110kV lines Safe distances for buildings and structures near conductors … conductors 7.5m 8.5m 10 m Engineering advice required 110kV Minimum Approach Distances Near 110kV Transmission Lines on Towers …
110kV Lines on towers
(PDF 135.56 KB)
Last updated: 18 Sep 2024
Minimum Approach Distances - 110kV Lines on Poles
… of conductors 9.5m 12.5m 21m Table 1 – 110kV lines Safe distances for buildings and structures near conductors … conductors 7.5m 8.5m 10m Engineering advice required 110kV Minimum Approach Distances Near 110kV Transmission Lines on Poles …
110kV Lines on Poles
(PDF 177.51 KB)
Last updated: 05 Jul 2023
NZ Electrical Code of Practice for Electrical Safe Distances (NZECP 34)
… NEW ZEALAND ELECTRICAL CODE OF PRACTICE for ELECTRICAL SAFE DISTANCES NZECP 34:2001 NEW ZEALAND ELECTRICAL CODE OF … SECTION 2 4 MINIMUM SAFE DISTANCES FOR EXCAVATION AND CONSTRUCTION NEAR … CONDUCTORS WITHOUT ENGINEERING ADVICE.............9 3.4 MINIMUM SAFE DISTANCES OF CONDUCTORS FROM BUILDINGS AND … 5.2 MINIMUM APPROACH DISTANCE …
Last updated: 05 Jul 2023
Electrical Hazard Management Plan - Civil Works
… lines. It is important to maintain safe separation distances from transmission lines to ensure: • The safety of … for Electrical Safe Distances (NZECP 34: 2001) sets out minimum safe electrical separation distance requirements. … sheet should be read in conjunction with the Minimum Approach Distance information sheets. A copy of NZECP34 is …
Info Sheet Civil EHMP.pdf
(PDF 627.17 KB)
Last updated: 05 Jul 2023
Safety Around Lines - Horticulture
… call 0800 843 474 (0800 THE GRID) Mobile plant: • The minimum approach distances to overhead transmission lines differ depending on …
Info Sheet - safety around Lines - horticulture - final.pdf
(PDF 446.03 KB)
Last updated: 26 Oct 2022
Mobile Plant and Transmission Lines
… lines. It is important to maintain safe separation distances from transmission lines to ensure: • The safety of … working area. • The reliability of the electricity supply. Minimum Safe Separation Distances for People and Mobile … persons working near transmission lines, the minimum safe approach distances limits are: 4 metres for 110 kV lines …
Info Sheet Mobile Plant.pdf
(PDF 410.28 KB)
Last updated: 12 Oct 2022
The Development Guide
… structures), and not meeting the required separation distances, can create unsafe situations and increase the … distances are breached. All mobile plant must remain a minimum of 4 metres from the lines at all times. People … people working near National Grid lines, the minimum safe approach distance limits are: for 110 kV lines and below – 4 …
Last updated: 05 Jul 2023
Working on Your Land
… takes place. To address these issues, we use a corridor approach to existing and new development. The National Grid … around it. Transpower seeks a National Grid Yard that is a minimum 12 metre setback either side of the centreline of a … important to always comply with the minimum safe separation distances set out in the New Zealand Electrical Code of …
Working on Your Land June 2020.pdf
(PDF 6.68 MB)